
CITY – GATES DROP TEST
All fire doors are required to be drop tested annually VISUAL INSPECTION Conduct a visual inspection for anything that may cause a hazard during testing
Conduct a visual inspection for anything that may cause a hazard during testing or affect proper operation or resetting.
Verify that:
Open and close the door using normal operation. If you find the door is not properly balanced, or there is damage or missing parts that may create a hazard or prevent proper operation, have these conditions corrected before conducting a drop test.
A drop test is required to confirm that the fire door will close automatically during a fire emergency. Use manufacturer’s drop test instructions. Door must be fully open before drop test. The door must close fully so the bottom bar rests o the sill. The average closing speed must be between 6″ and 24″ per second. Test each automatic closing option for the fire door.
Reset the door per manufacturer’s instructions. Open and close the door by normal operation, add tension back to spring. Drop test the door a second time, add tension back to spring and reset again. Ultimate acceptance of a fire door is the decision of the authority having jurisdiction, as defined in NFPA 80.
$ 749.00 Pass or Fail Prices for doors up to 200 square feet
All fire doors are required to be drop tested annually VISUAL INSPECTION Conduct a visual inspection for anything that may cause a hazard during testing
Shutters for parts windows, ticket counters or distribution windows SPECIFICATIONS Counter Fire Shutters are designed specifically for pass-thru openings requiring fire protection. These units, with
Rolling Steel Doors for Healthcare facilities and where fire separation is needed Product Description U. L. Labeled Fire Doors are rated closures for fire protection
Auto Reset Motors allow for easy drop testing when required Product Description Retrofit fire door operators provide state-of-the-art technology for existing rolling fire doors. When